BAS-SVP039C-EN
13
Table 2. SCC Network Variable Outputs (continued)
NV# Name SendHrtBt SNVT
Description
91
nvoFDD
SNVT_state Fault Detection and Diagnostics
nvoFDD.0
(MSB) Bit 0
Diagnostic: Not Economizing When
Should Be
nvoFDD.1 Bit 1
Diagnostic: Economizing When
Should Not
nvoFDD.2 Bit 2
Diagnostic: Excessive Outdoor Air
Flow
nvoFDD.3 Bit 3
Diagnostic: Mixed Air Low
Temperature Cycle
nvoFDD.4 Bit 4
Diagnostic: Mixed Air Temperature
Sensor Failure
nvoFDD.5 Bit 5
Diagnostic: Outdoor Air Damper Not
Modulating
nvoFDD.6 Bit 6
Diagnostic: Outdoor Air Temperature
Sensor Failure
nvoFDD.7 Bit 7
Diagnostic: Return Air Temperature
Sensor Failure
nvoFDD.8 Bit 8
Diagnostic: Supply Air Temperature
Sensor Failure
nvoFDD.9 Bit 9 Reserved
nvoFDD.10 Bit 10 Reserved
nvoFDD.11 Bit 11 Reserved
nvoFDD.12 Bit 12 Reserved
nvoFDD.13 Bit 13 Reserved
nvoFDD.14 Bit 14 Reserved
nvoFDD.15
(LSB) Bit 15
Reserved
92 nvoHeatCool
SNVT_hvac_mode
Heat Cool Mode Status
93
nvoHeatPrimary
SNVT_lev_percent Heating Capacity Primary Status
94
nvoHeatSecondary
SNVT_lev_percent Heating Capacity Secondary Status
95 nvoHumidifier
SNVT_lev_percent Humidification Capacity Status
96
nvoLocalCWTemp
SNVT_temp_p Condenser Water Temperature Local
97
nvoLocalSpaceTmp
SNVT_temp_p Space Temperature Local
98
nvoMixedAirTemp
SNVT_temp_p Mixed Air Temperature Local
99
nvoOADamper
SNVT_lev_percent Outdoor Air Damper Position
100
nvoOAEnthalpy
SNVT_enthalpy Outdoor Air Enthalpy Active
101 nvoOAFlow
FNVT_flow
Outdoor Air Flow Active
102 nvoOutdoorRH
SNVT_lev_percent Outdoor Air Humidity Active
103
nvoOutdoorTemp
SNVT_temp_p Outdoor Air Temperature Active
104
nvoRATemp
SNVT_temp_p Return Air Temperature
105 nvoRetFanOnOff
SNVT_switch
Return Fan Output Status
106 nvoRetFanPress
SNVT_press_p
Return Fan Air Pressure
107 nvoRetFanStatus
SNVT_switch
Return Fan Speed Status
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess