14
BAS-SVP039C-EN
Table 2. SCC Network Variable Outputs (continued)
NV# Name SendHrtBt SNVT
Description
108
nvoRTUStatus ♥
SNVT_state Rooftop Status
nvoRTUStatus.0 ♥
(MSB) Bit 0 Unit Running State
nvoRTUStatus.1 ♥ Bit 1
Emergency Stop
nvoRTUStatus.2 ♥ Bit 2
External Auto Stop Input Status
nvoRTUStatus.3 ♥ Bit 3
Condensate Overflow Input
nvoRTUStatus.4 ♥ Bit 4
Timed Override Status (with Bit 5)
nvoRTUStatus.5 ♥ Bit 5 Timed Override Status
00 Idle
01 On
10 Cancel
nvoRTUStatus.6 ♥ Bit 6 Precool Mode Status
nvoRTUStatus.7 ♥ Bit 7
Morning Warmup Running
nvoRTUStatus.8 ♥ Bit 8
Supply Air Tempering Status
nvoRTUStatus.9 ♥ Bit 9
Daytime Warmup Running
nvoRTUStatus.10 ♥ Bit 10 Reserved
nvoRTUStatus.11 ♥ Bit 11
Compressor Lockout Status
nvoRTUStatus.12 ♥ Bit 12
Coil Frost Protection Status, Circuit 1
nvoRTUStatus.13 ♥ Bit 13
Coil Frost Protection Status, Circuit 2
nvoRTUStatus.14 ♥ Bit 14
Rapid Restart Status
nvoRTUStatus.15 ♥
(LSB) Bit 15
Reserved
109
nvoSetpoint
♥
SNVT_temp_p Space Temperature Setpoint Local
110
nvoSpaceCO2
♥
SNVT_ppm Space CO2 Concentration Active
111
nvoSpaceEnthalpy
♥
SNVT_enthalpy Return Air Enthalpy Active
112
nvoSpaceRH
♥
SNVT_lev_percent Space Humidity Active
113
nvoSpaceTemp
♥
SNVT_temp_p Space Temperature Active
114
nvoStartsRunTmA ♥
UNVT_starts_runtime
Starts - Compressor 1A
♥
SNVT_count_f
Starts
♥
SNVT_time_f
Run Time
115
nvoStartsRunTmB ♥
UNVT_starts_runtime
Starts - Compressor 1B
♥
SNVT_count_f
Starts
♥
SNVT_time_f
Run Time
116
nvoStartsRunTmC ♥
UNVT_starts_runtime
Starts - Compressor 1C
♥
SNVT_count_f
Starts
♥
SNVT_time_f
Run Time
117
nvoStartsRunTmD ♥
UNVT_starts_runtime
Starts - Compressor 2A
♥
SNVT_count_f
Starts
♥
SNVT_time_f
Run Time
118
nvoStartsRunTmE ♥
UNVT_starts_runtime
Starts - Compressor 2B
♥
SNVT_count_f
Starts
♥
SNVT_time_f
Run Time
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess