18
BAS-SVP039C-EN
Table 4. DAC Network Variable Inputs (continued)
NV# Name Recv HrtBt SNVT
Description
64
nviRTUConfig
SNVT_state
Rooftop Configuration
nviRTUConfig.0 (MSB) Bit 0
Reserved
nviRTUConfig.1
Bit 1
Cooling Lockout
nviRTUConfig.2
Bit 2
Heating Lockout
nviRTUConfig.3
Bit 3
Demand Limit Request BAS
nviRTUConfig.4
Bit 4
Energy Consumption Reset
nviRTUConfig.5
Bit 5
Supply Fan Compensation
nviRTUConfig.6
Bit 6 PreCool Enable Command
nviRTUConfig.7
Bit 7
Morning Warmup Enable Command
nviRTUConfig.8
Bit 8
Supply Air Tempering Request BAS
nviRTUConfig.9
Bit 9
Daytime Warmup Enable Command
nviRTUConfig.10
Bit 10
Timed Override Request (with Bit 11)
nviRTUConfig.11
Bit 11
Timed Override Request
00 Idle
01 On
10 Cancel
11 Invalid
nviRTUConfig.12
Bit 12 Reserved
nviRTUConfig.13
Bit 13 Reserved
nviRTUConfig.14
Bit 14 Reserved
nviRTUConfig.15 (LSB) Bit 15
Reserved
65
nviRequest SNVT_obj_request Reset Diagnostic Request
66
nviSpaceCO2
♥
SNVT_ppm Space CO2 Concentration BAS
67
nviSpaceDehumSP SNVT_lev_percent Space Dehumidification Setpoint BAS
68
nviSpaceHumSP SNVT_lev_percent Space Humidification Setpoint BAS
69
nviSpaceRH
♥
SNVT_lev_percent Space Humidity BAS
70
nviSpaceTemp
♥
SNVT_temp_p Space Temperature BAS
71 nviTraneVar2
UNVT_c5c
Manufacturer-defined
Table 5. DAC Network Variable Outputs
NV# Name Send HrtBt SNVT
Description
72
nvoAlarmMessage SNVT_str_asc
Diagnostic Last Message
73
nvoApplicMode
♥
SNVT_hvac_mode
Application Mode Output
74
nvoBldgStatPress
♥
SNVT_press_p Space Static Pressure Active
75
nvoCondCap
♥
SNVT_lev_percent Condenser Capacity
76
nvoCoolPrimary
♥
SNVT_lev_percent Cooling Capacity Status
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess