Table 5. DAC Network Variable Outputs (continued)
NV# Name Send HrtBt SNVT
Description
77
nvoCprsrsRunning
SNVT_state
Compressor Status
nvoCprsrsRunning.0
(MSB) Bit 0 Validity of bit 8
nvoCprsrsRunning.1
Bit 1
Validity of bit 9
nvoCprsrsRunning.2
Bit 2
Validity of bit 10
nvoCprsrsRunning.3
Bit 3
Validity of bit 11
nvoCprsrsRunning.4
Bit 4
Validity of bit 12
nvoCprsrsRunning.5
Bit 5
Validity of bit 13
nvoCprsrsRunning.6
Bit 6
Validity of bit 14
nvoCprsrsRunning.7
Bit 7
Validity of bit 15
nvoCprsrsRunning.8
Bit 8
Compressor 1A Status
nvoCprsrsRunning.9
Bit 9
Compressor 1B Status
nvoCprsrsRunning.10
Bit 10
Compressor 1C Status
nvoCprsrsRunning.11
Bit 11
Compressor 1D Status
nvoCprsrsRunning.12
Bit 12
Compressor 2A Status
nvoCprsrsRunning.13
Bit 13
Compressor 2B Status
nvoCprsrsRunning.14
Bit 14
Compressor 2C Status
nvoCprsrsRunning.15
(LSB) Bit 15 Compressor 2D Status
78 nvoCWFlow
SNVT_switch
Condenser Water Flow Status
79
nvoCWPump
SNVT_switch
Condenser Water Pump Status
80
nvoCWTemp
SNVT_temp_p Condenser Water Temperature
81 nvoDAReheatSP
SNVT_temp_p Discharge Air Reheat Setpoint Active
82 nvoDehumidifier
SNVT_switch
Dehumidification Control Status
83
nvoDischAirTemp
SNVT_temp_p Discharge Air Temperature
84 nvoDuctStatPress
SNVT_press_p
Duct Static Pressure Active
85 nvoEconEnabled
SNVT_switch
Economizer Entering Water
Temperature Active
86 nvoEffDADewPtSP
SNVT_temp_p
Discharge Air Dewpoint Temperature
Setpoint Active
87
nvoEffDATempSP
SNVT_temp_p
Discharge Air Temperature Setpoint
Active
88 nvoEffDuctStatSP
SNVT_press_p Duct Static Pressure Setpoint Active
89
nvoEffectOccup
SNVT_occupancy Occupancy Status
90
nvoEffSpaceHumSP
SNVT_lev_percent Space Humidity Active
91
nvoEREABPDamper
SNVT_lev_percent
Energy Recovery Exhaust Air Bypass
Damper Position
92
nvoERLvgExhTemp
SNVT_temp_p
Energy Recovery Leaving Exhaust
Temperature Status
93
nvoEROABPDamper
SNVT_lev_percent
Energy Recovery Outdoor Air Bypass
Damper Status
94 nvoERPreheat
SNVT_switch
Energy Recovery Preheat Status
95 nvoERStatus
SNVT_switch
Energy Recovery Status
96
nvoExhDamper
SNVT_lev_percent Exhaust Damper Position
97 nvoExhFanOnOff
SNVT_switch
Exhaust Fan Output Status
98 nvoExhFanStatus
SNVT_switch
Exhaust Fan Speed Status
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess