UV-SVP01A-EN 37
Configuration
Occupied Bypass Timer
1. The occupied bypass timer is used for timed override applications.
Power-Up Control Wait
Maintenance Timers
Table 18: Bypass timer range
Default Valid range
Occupancy bypass timer
1
120 Minutes
0 to 240 minutes
(1 minute resolution)
Table 19: Control wait timer
Default Valid range
Power up control wait (2 minutes) 120 seconds Disable or enable
Table 20: Maintenance timer range
Default Valid range
Maintenance timer 0 0 to 10,000 hours