18-BC83D1-2 7
5.5 Reuse Existing Refrigerant Lines
For retrofit applications, where the existing
indoor evaporator coil and/or refrigerant lines
will be used, the following precautions should
be taken:
Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
Ensure that the refrigerant lines are free of
leaks, acid, and oil.
Important: For more information see publica-
tion number SS-APG006-EN.
CAUTION
!
If using existing refrigerant lines make certain that
all joints are brazed, not soldered.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise
within the building structure due to vibration
transmission from the refrigerant lines.
For Example:
When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Comply with National, State, and Local Codes when
isolating line sets from joists, rafters, walls, or other
structural elements.
Isolation From Joist/Rafter
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure
Liquid Line directly to Vapor line using tape, wire, or other appro-
priate method every 8 ft.
Joist/Rafter
Isolator
Line Set
8 Feet Maximum

Other manuals for Trane XR13

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane XR13 and is the answer not in the manual?

Trane XR13 Specifications

General IconGeneral
Sound Level74 dB
RefrigerantR-410A
StagesSingle-stage
SEER14
HSPF8.2
CompressorSingle-stage
Cooling Capacity1.5 - 5 tons
Warranty10 year limited warranty on compressor