NEWTON+ – Operational Manual
TRINITY
[14]
3. The unit will automatically reset and return into Run Mode. In case, your
setting is not completed, proceed the above instruction to specify for other
parameters
6. Setting the Time Delay in between stages
This is one type of digital dead band. During the Time Delay, the unit will not take
any control action. Hence the Time Delay is settable from 40 to 180 seconds.
1. In Run Mode, press
key for about 4 to 5 seconds and then the unit will
enter into Programming Mode. Press
key to receive the Time Delay such
as shown below.
2. Press
key. Immediately, P starts blinking which shows that the parameter
can now be changed. Set the desired Time Delay by pressing
and
keys and then, press
key to confirm the parameter setting.
3. In case, your setting is completed, press
key for about 4 to 5 seconds to
return into Run Mode. Or press
and keys to specify for other
parameters such as above instructions.
7. Setting On Delay with Lagging PF
In case of PF Control Action, On Delay is freely programmable from 10 to 20. If the
system PF falls below the target PF with lagging PF, the unit checks whether the
switching capacitor could be persistent or no. If target PF is not achieved, the relay
switches on the capacitor bank accordingly.
1. In Run Mode, press
key for about 4 to 5 seconds and then the unit will
enter into Programming Mode. Press
key to receive the On Delay such as
shown below.
2. Press
key. Immediately, P starts blinking which shows that the parameter
can now be changed. Set the desired On Delay by pressing
and keys
and then, press
key to confirm the parameter setting.
ON DELAY=10
TIME DELAY=40