Troubleshooting/Maintenance
Condition LCD Display
LED
Status
Audible
Alarm Explanation Solution
Overload
Green: On
Red: On
Yes Loads up to
100% run
continuously;
101%-120% for
1 minute; 120-
200% for 0.5
seconds.
If the load
demand from
the equipment
or device
being operated
exceeds the time
intervals listed,
the inverter will
sound an alarm
and shut down
the inverter
output.
Reduce load,
wait 3-5 minutes,
restart the
inverter by power-
cycling the ON/
OFF switch on the
unit or remote
(if equipped).
Alternatively,
reduce the load
and wait 4-6
minutes. The
inverter will
auto-recover
and resume
operation.
Over-
Temperature
Green: On
Red: On
Yes The thermal
resistor exceeds
176° F (80° C).
Allow the inverter
to cool. Do not
block the cooling
slots or airflow
over and through
the inverter.
The inverter will
automatically
resume operation
after internal
temperature goes
down to 140°F
+/- 41°F (60°C
+/- 5°C).