Installing
14
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
5 Installing
Fig.8: Vertical mounting Fig.9: Horizontal mounting
Depressurize the installation before mounting.
Do not install the device at a location where high pressure pulses can occur.
Fit the device to the pressure connection using the corresponding counterpiece as
shown in the figure.
Note the different pressure connections.
Mount the sensor in any direction.
The display of the unit can be rotated by 180°.
The maximum tightening torque for fastening the sensor is 35 Nm (15 Nm for 7/16 UNF).
The housing can be rotated by 340°.
Severe temperature changes in the environment of the sensor can cause the shifting of the
zero point. In this case, the displayed measured value will not be zero when the sensor is in a
depressurized state. If the zero point is offset, an offset value can be set via the CoF parameter
(see chapter “Settings”).