9.1.4 Parameters in the main menu
Explanation Options Function
Uni
Display unit bar bar
psi psi
kPa kPa
MPa MPa
Ud1 mBar
Ud2 Torr = mmHg (0°C)
Ud3 Inch of water (60°F)
Ud4 Inch of water (39°F)
Ud5 Foot of water (39°F)
Ud6 Inch of Hg (60°F)
Ud7 Inch of Hg (32°F)
Ud8 mH20 (16°C)
Ud9 mH20 (4°C)
Ud10 kg/Cm
2
ou1
Function of output 1 Hno Hysteresis function (NO contact)
Hnc Hysteresis function (NC contact)
Fno Window function (NO contact)
Fnc Window function (NC contact)
SP1
Switching point 1 for hysteresis
function
ou1: Hno/Hnc
Upper limit value at which output 1 changes
its switching state when the pressure increases
rP1
Reset switching point 1
for hysteresis function
ou1: Hno/Hnc
Lower limit value at which output 1 changes
its switching state when the pressure drops
FH1
Upper switch point for window
function
ou1: Fno/Fnc
Upper switch point at which output 1 changes
its switching state
FL1
Lower switch point for window
function
ou1: Fno/Fnc
Lower switch point at which output 1 changes
its switching state
ou2
Function of output 2 Hno Hysteresis function (N/O = NO contact)
Hnc Hysteresis function (N/C = NC contact)
Window function Fno Window function (N/O = NO contact)
Fnc Window function (N/C = NC contact)