PowerSeries Pro Installation Guide
Notes for EN50136-1:2012 compliant installations - Applicable to integrated phone line and Ethernet communicator only.
The communicator operates in pass-through mode and it does acknowledge the alarm to the compatible control panel after an acknowledgement has been
received from the compatible alarm receiver.
1. The integrated communicator is monitored by the control panel and is programmed via the menu available from the compatible keypad connected
to the alarm control panel HS3248, HS3128, HS3023.
2. The communicaton path is immune to conducted and radiated RF fields, with levels up to 10V/m as tested per EN50130-4 Standard.
3. The control panel with integrated communication module conforms with radiated emissions levels for Class B equipment as per standards
EN61000-6-3/EN55032/CISPR32.
4. The control panel has two integrated communication paths: Phone line dialer and Ethernet (IP) communication path. These can be used in an
ATS with the following categories:
l Single Path mode SP3 (Phone line dialer) or SP4 (IP path), or
l Dual Path mode DP2 integrated Ethernet (IP) path in conjunction with the compatible control panel HS3248/HS3128/HS3032
integrated PSTN communicator, or
l Dual Path DP3 integrated Ethernet (IP) path in conjunction with the plug-in cellular module 3G9080-EU or GS9080.
5. The integrated Ethernet (IP) communication path uses sequential authentication for substitution security and encryption AES128 bit for inform-
ation security. The AES128-bit key is validated by NIST, Certificate No. 5371.
6. The integrated communicators have been tested for compliance in conjunction with the following applicable standards: EN50136-1:2012,
EN50136- 2:2013, EN50131-10:2014, Grade 3, Class II, ATS configuration: SP3, DP2, DP3. For EN50131-1:2006/A1:2009 /A2:2017 com-
pliant installations, the following programming options must be set as described: Supervision heartbeat set to 180 seconds for SP4 and DP3 con-
figuration, along with the ARC receiver supervison window set to 180 seconds. For DP2 configuration, the supervison must be set to 30
minutes.
This product is in conformity with the Electromagnetic Compatibility Directive 2014/30/EU, the Low Voltage Directive 2014/35/EU, and the RoHS3
Directive (EU) 2015/863.
The product is labelled with the CE mark as proof of compliance with the above mentioned European Directives. Also, a CE declaration of conformity
(DoC) for this product can be found at www.dsc.com under the Agency Listings section.
SIA False Alarm Reduction Installations: Quick Reference
Minimum required system consists of one Control unit model HS3032, HS3128 or HS3248, and any one of the compatible listed keypads (refer to page
1.).
The following wireless keyfobs can also be used in SIA compatible installations: PG9929, PG9939,PG9949.
Note: For models PG9929 and PG9939, the panic/emergency key shall be disabled for SIA compliant installations.
For a list of the default values programmed when the unit is shipped from the factory, and for other programming information, refer to the following
table.
The following optional subassembly modules also bear the SIA CP-01-2014 classification and may be used if desired: HSM2108 zone expander,
HSM2208 PGM output module, HSM2300 auxiliary power supply, HSM2204 output module, HSM2HOST9 2-way wireless transceiver, PG9901
indoor siren, PG9911 outdoor siren, and LE9080/3G9080/3H9080 cellular and PSDN communication module.
Caution
l For SIA FAR installations use only modules/devices that are listed on this page.
l Fire Alarm Verification feature (Auto Verified Fire Zone type [025]) is not supported on 2-wire smoke detectors zones, model FSA-210B(T)
(S)(ST)(LST)(R)(RT)(RD)(RST)(LRST). This feature may be enabled for 4-wire smoke detectors only (FSA-410B(T)(S)(ST)(LST)(R)(RT)
(RST)(LRST) and wireless detectors PG9916/PG9926). The fire alarm delay is 60s.
l Call Waiting Cancel (Section [382], option 4) on a non-Call Waiting line will prevent successful communication to the supervising station.
l All system smoke detectors must be tested annually by conducting an Installer Walk Test. Prior to exiting Walk Test mode, a sensor reset must
be done on the system, [*][7][2], to reset all latching 4-wire smoke detectors. Refer to the installation instructions supplied with the detector for
details.
Notes
l Programming at installation may be subordinate to other UL requirements for the intended application.
l Cross zones have the ability to individually protect the intended area (e.g. motion detectors which overlap).
l Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.
l This control panel has a communication delay of 30 seconds. It can be removed or increased up to 45 seconds by the end user with installer con-
sultation.
l The system shall be installed with the sounding device activated and the communicator enabled for transmission using SIA or CID format.
l ULC commercial burglary installations require DEOL resistors.
- 31 -