TST-100 Touchscreen Terminal Installation Guide 8
Supervision wiring
Figure 2:Supervised wiring
In RM protocol mode, this method reports:
Short
Normal: 1K for Normally Open, 1K for Normally Closed
Alert: 500 ohms for Normally Open, and 2K for Normally Closed
Open: >30K
Line Fault: Any unexpected value usually due to wrong value or fault resistors
In Smart protocol mode, the data state resistances can be configured from the host, using the same resistance wiring
configurations that are available for the I/8-CSI and the IP-ACM v1 or IP-ACM v2.
For more information regarding other inputs available and details of configuration, refer to the
I/8-CSI User Guide
.