2.4.1 - TECHNICAL DATA ACCORDING TO ErP DIRECTIVE
MODULEX
EXT 348 EXT 440 EXT 550 EXT 660 EXT770 EXT 900
Element Symbol Unit
Eective nominal output Prated kW 342 424 530 636 743 849
Seasonal energy eciency of
central heating
ƞ
s % 93
Season eciency class for
heating
A * * * * *
For boilers for central heating
and mixed boilers:
eective heat output
Eective heat output with
high temperature capacity
(Tr 60 °C / Tm 80 °C)
P
4 kW 341.7 - - - - -
Rated heat output eciency
with high temperature capacity
(Tr 60 °C / Tm 80 °C)
ƞ
4 % 88.5 - - - - -
Eective output at 30% of the rated heat
output with low temperature
capacity (Tr 30 °C)
P
1 kW 11.5 - - - - -
Performance at 30% of the rated heat
output with low temperature
capacity (Tr 30 °C)
ƞ
1 % 96.2 - - - - -
Boiler with output range adjustment: YES / NO NO NO NO NO NO NO
Auxiliary electricity consumption
With a full load elmax kW 0.393 0.626 0.783 0.940 1.096 1.252
With a partial load elmin kW 0.054
Standby mode P
SB kW 0.020
Other elements
Heat dispersion on standby P
stb kW 0.2114 0.2114 0.2114 0.2114 0.2114 0.2114
Nitrogen oxides emissions ref. PCS NOx
Mg/kWh
49
NOx class 6
Annual electricity consumption Q
HE GJ 1050 1303 1633 1959 2286 2612
For mixed heating appliances
Declared load prole - - - - - - -
Water heating
energy eciency
ƞ
wh % - - - - - - -
Daily consumption of electricity Qelec kWh - - - - - - -
Daily consumption of fuel Qfuel kWh - - - - - - -
Internal sound power level Lwa dB (A) - - - - - - -
Annual electricity consumption AEC kWh - - - - - - -
Annual fuel consumption AFC GJ - - - - - - -
Seasonal DHW eciency class
- - - - - - -