• CFG
• InFo Display
upd
(.xd
err
INF
Software
version
Self diagnostic
error code
Configuration
hrd
+8 error OUT2 card recognition
+16 error OUT3 card recognition
Information
display
0 No Error
1 Lo
2 Hi
3 ERR
4 SBR
OUTPUT 2
0 = None
1 = Relay
OUTPUT 3
0 = None
1 = Relay
SERIAL COMMUNICATION
0 = None
110
h.pb
h.it
h.dt
h.p.x
h.p.l
rst
P.rs
A.rs
ffd
sof
lb.t
lb.p
fa.p
g.sp
Proportional band for
heating or hysteresis in
regulation ON/OFF
Integral time for heating
Derivative time for
heating
Maximum power limit for
heating
Manual reset
Waiting time for LBA alarm intervention
(Set to “0” to disable LBA alarm)
Power limit for LBA
alarm condition
Power output in fault condition
(when probe is faulty)
-999 ... 999
punti scala
0 ... 999.9% f.s.
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
Minimum power limit
for heating
(not available for double heat/
cool action)
0.0 ... 100.0%
0.0 ... 500.0 min
-100.0 ... 100.0%
-100.0 ... 100.0%
ON / OFF
Set gradient
(see applicable note)
0.0...999.9 digit/min.
(digit / sec see SP.r)
Antireset
Feedforward
0 ... 9999
scale points
-100.0 ... 100.0%
Reset power -100.0 ... 100.0%
Softstart time 0.0 ... 500.0 min
(*)
(*)
(*) LBA alarm may be reset by simultaneously pressing Δ + ∇ keys when OutP is
displayed or by switching to Manual.
S.tv
CFG
Control parameters
(*) +16 with passage automatic rifle in GO if PV-SP > 0,5%
+32 with passage automatic rifle in GO if PV-SP > 1%
+64 with passage automatic rifle in GO if PV-SP > 2%
+128 with passage automatic rifle in GO if PV-SP > 4%
Enabling
self-tuning,
autotuning,
softstart
S.tun Continuous Sel-ftuning Softstart
autotuning
0 NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
5 YES NO YES
6 - - -
7 - - -
S.tun Autotuning Selftuning Softstart
one shot
8* WAIT NO NO
9 GO NO NO
10* WAIT YES NO
11 GO YES NO
12* WAIT NO YES
13 GO NO YES
g.s0
Setpoint gradient of
pre-heating
0.0 ... 999.9 digit / min.
(digit / sec seeSP.r)
Xt.0
Retention time of
pre-heating setpoint
0 … 200 min.
(sec see SP.r)
sp.0
Setpoint of pre-heating
Lo.L … Hi.L
g.s1
Set gradient at the end of
the pre-heating
0.0 ... 999.9 digit / min.
(digit / sec see SP.r)
0
1.2
5.83
1.33
100.0
0.0
0
0.0
0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0.0
0.0
4 80379_MHW_600V-T73_06-2012_ENG