UP-2210 Hardware installation and configuration manual
74
B. Use the active setting.
You can use the active settings and modify this and then save as a new configuration.
In example above, Figure 65, the primary voltage is 11 kV and the secondary 110 V.
The meter calculates the ratio to 100.
The current transformer ratio is 400:5 and is entered as in the picture above.
Press Next.
Tip! You can use if you for example want to start over again.
Enter settings you want as in Figure 66. Then press Next and you will get a summary of measure
configuration, see Figure 67 below.
Figure 65
Figure 66
Information about the actual
highlighted parameter.