ENGLISH
- 37 -
PARAMETER VALUE DESCRIPTION DEFAULT MEMO
t.AP1
Leaf 1 opening time
22.5”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes
t.AP2
Leaf 2 opening time
22.5”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes.
WARNING: if motor 2 is not connected, this time must be set to
zero
t.APP
Partial opening time (pedestrian access)
6.0”
0.0”-1’00
When the control unit receives a Start Pedestrian command, it will open
leaf 1 only, for a shorter time. Max allowed time to be setup is t.AP1
t.Ch1
Leaf 1 closing time
23.5”
0.0”-5’00
Tempo regolabile da 0 secondi a 5 minuti
NOTA: Per evitare che l’anta non si chiuda completamente, è consigliabile
impostare un tempo più lungo di quello di apertura t.AP1
t.Ch2
Tempo di chiusura anta 2
23.5”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes.
NOTE: To avoid that the door does not close completely, we recommend
to setup a longer time than t.AP2 opening time.
t.ChP
Partial closing time (pedestrian access)
7.0”
0.0” - 2’00
When the control unit receives a Start Pedestrian command, it will use this
time to close the gate. Max allowed time to be setup is t.Ch1.
NOTE: To avoid that the door does not close completely, we recommend
to setup a longer time than t.APP opening time
t.C2P
Leaf 2 closing time during pedestrian cycle
no
0.5” - 5.0”
During a partial opening cycle (pedestrian access) leaf 2 may move slightly
because of the wind or its own weight; in this case at closing time leaf 1
could hit leaf 2 and the gate would remain not perfectly closed.
To avoid this, in the last seconds of the cycle a light closing force is applied
to leaf 2 too.
no
Function deactivated
r.AP
Opening door delay
1.0”
0.0” - 1’00
During the opening phase, leaf 1 must start moving before leaf 2, to avoid
that both doors may collide.
Leaf 2 opening will be delayed for the setup time
r.Ch
Closing door delay
3.0”
0.0” - 1’00
During the closing phase, leaf 1 must start moving after leaf 2, to avoid
that both doors may collide.
Leaf 1 closing will be delayed for the setup time
t.SEr
Lock time
2.0”
0.5”- 1’00
Before the opening phase begins, the control unit will energize the electric
lock in order to release it and enable the gate motion. t.SEr time will fix
the energizing time.
m WARNING: in case the gate has no electric lock, set the value
no
no
Function deactivated
SEr.S
Silent Locking Mode
Si
Si
Function activated
no
Function deactivated