EasyManua.ls Logo

Vacon 20 - 3.1.3 Power losses

Vacon 20
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
monitoring & parameters vacon 25
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
P3.4 Preset speed 0 P3.1 P3.2 Hz 5.00 180
Preset speed 0 is used
as frequency reference
when P3.3 = 1
P3.5 Preset speed 1 P3.1 P3.2 Hz 10.00 105
Activated by digital
inputs
P3.6 Preset speed 2 P3.1 P3.2 Hz 15.00 106
Activated by digital
inputs
P3.7 Preset speed 3 P3.1 P3.2 Hz 20.00 126
Activated by digital
inputs
Acceleration
time 1
0.1 3000.0 s 3.0 103
Acceleration time from
0 Hz to maximum fre-
quency.
Deceleration
time 1
0.1 3000.0 s 3.0 104
Deceleration time from
maximum frequency to
0 Hz.
P6.1 AI1 Signal range 0 1 0 379
0 = 0 - 100%
1 = 20% - 100%
20% is the same as 2 V
minimum signal level.
P6.5 AI2 Signal range 0 1 0 390
0 = 0 - 100%
1 = 20% - 100%
20% is the same as 2 V
or 4 mA minimum signal
level.
Automatic reset 0 1 0 731
0 = Disable
1 = Enable
P17.2
Parameter
conceal
01 1 115
0 = All parameters visi-
ble
1 = Only quick setup
parameter group visible
Code Parameter Min Max Unit Default ID Note