monitoring & parameters vacon • 25
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
P3.4 Preset speed 0 P3.1 P3.2 Hz 5.00 180
Preset speed 0 is used
as frequency reference
when P3.3 = 1
P3.5 Preset speed 1 P3.1 P3.2 Hz 10.00 105
Activated by digital
inputs
P3.6 Preset speed 2 P3.1 P3.2 Hz 15.00 106
Activated by digital
inputs
P3.7 Preset speed 3 P3.1 P3.2 Hz 20.00 126
Activated by digital
inputs
Acceleration
time 1
0.1 3000.0 s 3.0 103
Acceleration time from
0 Hz to maximum fre-
quency.
Deceleration
time 1
0.1 3000.0 s 3.0 104
Deceleration time from
maximum frequency to
0 Hz.
P6.1 AI1 Signal range 0 1 0 379
0 = 0 - 100%
1 = 20% - 100%
20% is the same as 2 V
minimum signal level.
P6.5 AI2 Signal range 0 1 0 390
0 = 0 - 100%
1 = 20% - 100%
20% is the same as 2 V
or 4 mA minimum signal
level.
Automatic reset 0 1 0 731
0 = Disable
1 = Enable
P17.2
Parameter
conceal
01 1 115
0 = All parameters visi-
ble
1 = Only quick setup
parameter group visible
Code Parameter Min Max Unit Default ID Note