monitoring & parameters vacon 27
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
Brake Chopper 0 2 0 504
0 = Disabled
1 = Enabled: Always
2 = Run state
Brake chopper
level
0 911 V varies 1267
Brake chopper control acti-
vation level in volt.
For 240V Supply:
240*1.35*1.18 = 382V
For 400V Supply:
400*1.35*1.18 = 638V
Please note that when
brake chopper is used the
overvoltage controller can
be switched off or the over-
voltage reference level can
be set above the brake
chopper level.
Motor
identification
02 0 631
0 = Not active
1 = Standstill identification
(need run command within
20 s to activate)
2 = Identification with run
(need run command within
20 s to activate. Only availa-
ble in power SW V026
included in FW01070V010
or later version)
Rs voltage drop 0.00
100.0
0
%0.00662
Voltage drop over motor
windings as % of U
nmot
at
nominal current.
Overvoltage
controller
02 1 607
0 = Disabled
1 = Enabled, Standard
mode
2 = Enabled, Shock load
mode
Undervoltage
controller
01 1 608
0 = Disable
1 = Enable
Sine filter 0 1 0 522
0 = Not in use
1 = In use
Code Parameter Min Max Unit Default ID Note
Table 6: Motor settings
P1.17
P1.18
P1.19
P1.20
P1.21
P1.22
P1.23