28 vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
NOTE!
* These parameters are only available in power SW FWP00001V026 included in
FW0107V010 or later version.
** Not more visible in version FW0107V012.
NOTE! These parameters are shown, when P17.2 = 0.
Modulator
type**
0 65535 28928 648
Modulator configuration word:
B1 = Discontinuous modu-
lation (DPWMMIN)
B2 = Pulse dropping in
overmodulation
B6 = Under modulation
B8 = Instantaneous DC volt-
age compensation *
B11 = Low noise
B12
= Dead time compensation *
B13
= Flux error compensation *
* Enabled by default
Efficiency opti-
mization*
0 1 0 666
Energy optimization,
the frequency converter seach
for the minimum cuuren in
order to save energy and lower
motor
noise
0 =
disabled
1 =
enable
I/f start enable* 0 1 0 534
0 =
disabled
1 =
enable
I/f start fre-
quency refer-
ence limit*
1 100 % 10 535
Output frequency limit
below which the defined I/f
start current is fed to motor.
I/f start current
reference*
0 100.0 % 80.0 536
Current reference in percent of
motor nominal current [1 =
0.1%]
Voltage limiter
enable*
0 1 1 1079
Select voltage limiter mode:
0 =
Disabled
1 =
Enabled
P1.30 Start delay time 0 16.00 s 0 1499
NOTE!
The delay time
between run request is given
and drive go to running.
0
= not used
Code Parameter Min Max Unit Default ID Note
Table 6: Motor settings
P1.24
P1.25
P1.26
P1.27
P1.28
P1.29