monitoring & parameters vacon • 29
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.4 Start / stop setup (Control panel: Menu PAR -> P2)
Code Parameter Min Max Unit Default ID Note
P2.1
Remote Control
Place Selection
0
20172
0 = I / O terminals
1 = Fieldbus
2 = Keypad
Start function
0
10505
0 = Ramp
1 = Flying start
Stop function
0
10506
0 = Coasting
1 = Ramp
P2.4
I / O Start / Stop
logic
04 2 300
I / O control I / O control
signal 1 signal 2
0 Forward Reverse
1 Fwd(edge) Inverted Stop
2 Fwd(edge) Bwd(edge)
3 Start Reverse
4 Start(edge) Reverse
P2.5 Local / Remote 0 1 0 211
0 = Remote control
1 = Local control
P2.6
Keypad control
direction
01 0 123
0 = Forward
1 = Reverse
P2.7
Keypad stop but-
ton
01 1 114
0 = Keypad control only
1 = Always
P2.8
Remote Control
Place 2 Selection
0
20173
0 = I / O terminals
1 = Fieldbus
2 = Keypad
keypad button
lock
0
1 0 15520
0 = unlock all keypad button
1 = Loc/Rem button locked
P2.10
Keypad reverse
enable
0
1 0 1500
0 = Reverse enabled
1 = Reverse disabled
Table 7: Start / stop setup