32 vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
P4.13
Accel2 Frequency
Threshold
0.00 P3.2 Hz 0.00 527 0.00 = disabled
P4.14
Decel2 Frequency
Threshold
0.00 P3.2 Hz 0.00 528 0.00 = disabled
P4.15
External Brake:
Open Delay
0.00 320.00 s 0.20 1544
Delay to open brake
after Open frequency
limit is reached.
P4.16
External Brake:
Open Frequency
limit
0.00 P3.2 Hz 1.50 1535
Opening frequency from
forward and reverse
direction.
P4.17
External Brake :
Close Frequency
limit
0.00 P3.2 Hz 1.00 1539
Close frequency from
positive direction if no
run command active.
P4.18
External Brake :
Close Frequency
limit in Reverse
0.00 P3.2 Hz 1.50 1540
Close frequency from
negative direction if no
run command active.
P4.19
External Brake :
Open/Close Cur-
rent limit
0.0 200.0 % 20.0 1585
The brake is not opened
if the current does not
exceed this value, and is
closed immediately if
current goes below.
This parameter is set as
a percent of Motor nomi-
nal current.
P4.20
Quick stop deceler-
ation time
0,1 3000,0 s 2,0 1259
Deceleration time for
quick stop (for digin or
fieldbus)
Code Parameter Min Max Unit Default ID Note
Table 9: Ramps and brakes setup