monitoring & parameters vacon • 37
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.11 Analogue outputs (Control panel: Menu PAR -> P9)
P8.13
DOE4 signal
selection
0 Varies 0 1390
See 8.1, hidden until an
option board is connected
P8.14
DOE5 signal
selection
0 Varies 0 1391
See 8.1, hidden until an
option board is connected
P8.15
DOE6 signal
selection
0 Varies 0 139
See 8.1, hidden until an
option board is connected
Code Parameter Min Max Unit Default ID Selections
P9.1
Analogue output
signal selection
0 14 1 307
0 = Not used
1 = Output freq (0-f
max
)
2 = Output current (0-I
nMotor
)
3 = Motor torque (0-T
nMotor
)
4 = PID output (0 - 100%)
5 = Freq refer. (0-f
max
)
6 = Motor speed (0-n
max
)
7 = Motor power (0-P
nMotor
)
8 = Motor Voltage (0-U
nMotor
)
9 = DC-link Voltage
(0 - 1000 V)
10 = Process Data In1
(0 - 10000)
11 = Process Data In2
(0 - 10000)
12 = Process Data In3
(0 - 10000)
13 = Process Data In4
(0 - 10000)
14 = Test 100%
P9.2
Analogue output
minimum
0 1 0 310
0 = 0 V / 0 mA
1 = 2 V / 4 mA
P9.3
Analogue output
scaling
0.0 1000.0 % 100.0 311 Scaling factor
P9.4
Analogue output
filter time
0.00
10.00 s 0.10 308 Filter time
P9.5
Analogue output
E1 signal selec-
tion
0
14 0 472
See P9.1, hidden until an
option board is connected
P9.6
Analogue output
E1 minimum
0
1 0 475
See P9.2, hidden until an
option board is connected
Table 14: Analogue outputs
Code Parameter Min Max Unit Default ID Selections
Table 13: Digital outputs