36 vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5.10 Digital outputs (Control panel: Menu PAR -> P8)
Code Parameter Min Max Unit Default ID Selections
P8.1
RO1 signal
selection
0Varies 2 313
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault Inverted
5 = Warning
6 = Reversed
7 = At Speed
8 = Motor regulator active
9 = FB Control Word.B13
10 = FB Control Word.B14
11 = FB Control Word.B15
12 = Output freq superv.
13 = Output torque superv.
14 = Unit temperature superv.
15 = Analogue input superv.
16 = Preset Speed Active
17 = External Brake ctrl
18 = Keypad control active
19 = I / O control active
20 = Temperature supervision
P8.2
RO2 signal
selcetion
0Varies 3 314See 8.1
P8.3
DO1 signal
selcetion
0Varies 1 312See 8.1
P8.4 RO2 inversion 0 1 0 1588
0 = No inversion
1 = Inverted
P8.5 RO2 ON delay 0.00 320.00 s 0.00 460 0.00 = No delay
P8.6 RO2 OFF delay 0.00 320.00 s 0.00 461 0.00 = No delay
P8.7 RO1 inversion 0 1 0 1587
0 = No inversion
1 = Inverted
P8.8 RO1 ON delay 0.00 320.00 s 0.00 458 0.00 = No delay
P8.9 RO1 OFF delay 0.00 320.00 s 0.00 459 0.00 = No delay
P8.10
DOE1 signal
selection
0Varies 0 317
See 8.1, hidden until an
option board is connected
P8.11
DOE2 signal
selection
0Varies 0 318
See 8.1, hidden until an
option board is connected
P8.12
DOE3 signal
selection
0 Varies 0 1386
See 8.1, hidden until an
option board is connected
Table 13: Digital outputs