monitoring & parameters vacon • 35
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.9 Pulse train / Encoder (Control panel: Menu PAR -> P7)
Code Parameter Min Max Unit Default ID Note
P7.1
Min pulse fre-
quency
0 10000 Hz 0 1229
Pulse frequency to be
interpreted as a 0% sig-
nal.
P7.2
Max pulse fre-
quency
0.0 10000 Hz 10000 1230
Pulse frequency to be
interpreted as a 100%
signal.
P7.3
Freq ref at min
pulse freq
0.00
P3.2 Hz 0.00 1231
Frequency correspond-
ing to 0% if used as fre-
quency reference.
P7.4
Freq ref at max
pulse freq
0.00
P3.2 Hz
50.00 /
60.00
1232
Frequency correspond-
ing to 100% if used as
frequency reference.
P7.5
Encoder direc-
tion
0 2 0 1233
0 = Disable
1 = Enable / Normal
2 = Enable / Inverted
P7.6
Encoder pulses
/ revolution
1 65535 ppr 256 629
Pulse count of encoder
per round. Used for scal-
ing encoder rpm monitor
value only.
Config DI5 and
DI6
0
2 0 1165
0 = DI5 and DI6 are for
normal digital input
1 = DI6 is for pulse train
2 = DI5 and DI6 are for
encoder frequence mode
Table 12: Pulse train/Encoder