34 vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5.8 Analogue inputs (Control panel: Menu PAR -> P6)
P5.17
Motor Preheat
Active
0 Varies 0 1044
Activates the Motor Pre-
heat (DC-Current) in
stop state when parame-
ter Motor Preheat func-
tion is set to 2
See 5.1
P5.18 Quick stop open 0 Varies 0 1213 As parameter 5.1
Code Parameter Min Max Unit Default ID Note
P6.1 AI1 Signal range 0 1 0 379
0 = 0 - 100% ( 0 - 10 V)
1 = 20% - 100% ( 2 - 10 V)
P6.2 AI1 Custom min
-100.00
100.00 % 0.00 380 0.00 = no min scaling
P6.3 AI1 Custom max
-100.00
300.00 % 100.00 381 100.00 = no max scaling
P6.4 AI1 filter time 0.0 10.0 s 0.1 378 0 = no filtering
P6.5 AI2 signal range 0 1 0 390 See P6.1
P6.6 AI2 Custom min
-100.00
100.00 % 0.00 391 See P6.2
P6.7 AI2 Custom max
-100.00
300.00 % 100.00 392 See P6.3
P6.8 AI2 filter time 0.0 10.0 s 0.1 389 See P6.4
P6.9 AIE1 Signal range 0 1 0 143
See P6.1, hidden until an
option board is con-
nected
P6.10 AIE1 Custom Min
-100.00 100.00
%
0.00
144
See P6.2, hidden until an
option board is con-
nected
P6.11 AIE1 Custom Max
-100.00 300.00
%
100.00
145
See P6.3, hidden until an
option board is con-
nected
P6.12 AIE1 Filter time
0.0 10.0
s
0.1
142
See P6.4, hidden until an
option board is con-
nected
Table 11: Analogue inputs
Code Parameter Min Max Unit Default ID Note
Table 10: Digital inputs