monitoring & parameters vacon 39
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.12 Fieldbus Data-Mapping (Control panel: Menu PAR -> P10)
Code Parameter Min Max Unit Default ID Note
P10.1
FB Data Output 1
selection
0 Varies 0 852
0 = Frequency reference
1 = Output reference
2 = Motor speed
3 = Motor current
4 = Motor voltage
5 = Motor torque
6 = Motor power
7 = DC link voltage
8 = Active fault code
9 = Analogue AI1
10 = Analogue AI2
11 = Digital input state
12 = PID feedback value
13 = PID setpoint
14 = Pulse train /
encoder input(%)
15 = Pulse train /
encoder pulse()
16 = AIE1
P10.2
FB Data Output 2
selection
0
Varies 1 853 Variable mapped on PD2
P10.3
FB Data Output 3
selection
0
Varies 2 854 Variable mapped on PD3
P10.4
FB Data Output 4
selection
0
Varies 4 855 Variable mapped on PD4
P10.5
FB Data Output 5
selection
0
Varies 5 856 Variable mapped on PD5
P10.6
FB Data Output 6
selection
0
Varies 3 857 Variable mapped on PD6
P10.7
FB Data Output 7
selection
0
Varies 6 858 Variable mapped on PD7
P10.8
FB Data Output 8
selection
0
Varies 7 859 Variable mapped on PD8
P10.9
Aux CW Data In
selection
0
5 0 1167
PDI for Aux CW
0 = Not used
1 = PDI1
2 = PDI2
3 = PDI3
4 = PDI4
5 = PDI5
Table 15: Fieldbus Data-Mapping