40 • vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5.13 Prohibited Frequencies (Control panel: Menu PAR -> P11)
5.14 Limit Supervisions (Control panel: Menu PAR -> P12)
Code Parameter Min Max Unit Default ID Note
P11.1
Prohibit Frequency
Range 1 Low Limit
0.00 P3.2 Hz 0.00 509
Low Limit
0.00 = Not used
P11.2
Prohibit Frequency
Range 1 High Limit
0.00 P3.2 Hz 0.00 510
High Limit
0.00 = Not used
P11.3
Prohibit Frequency
Range 2 Low Limit
0.00 P3.2 Hz 0.00 511
Low Limit
0.00 = Not used
P11.4
Prohibit Frequency
Range 2 High Limit
0.00 P3.2 Hz 0.00 512
High Limit
0.00 = Not used
Table 16: Prohibited Frequencies
Code Parameter Min Max Unit Default ID Note
P12.1
Output freq
supervision
function
0 2 0 315
0 = Not used
1 = Low limit
2 = High limit
P12.2
Output freq
supervision limit
0.00 P3.2 Hz 0.00 316
Output frequency super-
vision threshold
P12.3
Torque supervi-
sion function
0 2 0 348
0 = Not used
1 = Low limit
2 = High limit
P12.4
Torque supervi-
sion limit
0.0 300.0 % 0.0 349
Torque supervision
Threshold
P12.5
Unit Temperature
Supervision
0 2 0 354
0 = Not used
1 = Low limit
2 = High limit
P12.6
Unit Temperature
Supervision Limit
-10 100
°C
40 355
Unit temperature super-
vision threshold
P12.7
Analogue input
superv signal
0 Varies 0 356
0 = AI1
1 = AI2
2 = AIE1
P12.8 AI superv ON level 0.00 100.00 % 80.00 357 ON threshold AI superv.
P12.9
AI superv OFF
level
0.00 100.00 % 40.00 358 OFF threshold AI superv.
Table 17: Limit Supervisions