monitoring & parameters vacon 41
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
5.15 Protections (Control panel: Menu PAR -> P13)
P12.10
Temperature
supervision input
1 7 1 1431
Binary-coded selection
of signals to use for tem-
perature supervision
B0 = Temperature input 1
B1 = Temperature input 2
B2 = Temperature input 3
NOTE! Hidden until an
option board is con-
nected
P12.11
Temperature
supervision
function
0 2 2 1432
See 12.1, hidden until an
option board is con-
nected
P12.12
Temperature
supervision limit
-50.0/
223.2
200.0/
473.2
80.0 1433
Temperature supervision
threshold, hidden until
an option board is con-
nected
Code Parameter Min Max Unit Default ID Note
P13.1
Analogue Input
low fault
0 4 1 700
0 = No action
1 = Alarm
2 = Alarm, preset alarm
frequency
3 = Fault: Stop function
4 = Fault: Coast
Under voltage
fault
1 2 2 727
1 = No response (no fault
generated but drive still
stops modulation)
2 = Fault:Coast
Earth fault
0
3 2 703
0 = No action
1 = Alarm
2 = Fault: Stop function
3 = Fault: Coast
Output Phase
Fault
0
3 2 702 See 13.3
Stall protection
0
3 0 709 See 13.3
Under load pro-
tection
0
3 0 713 See 13.3
Motor thermal
protection
0
3 2 704 See 13.3
Table 18: Protections
Code Parameter Min Max Unit Default ID Note
Table 17: Limit Supervisions
P13.2
P13.3
P13.4
P13.5
P13.6
P13.7