monitoring & parameters vacon • 43
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
5
NOTE!
* These parameters are only available in power SW FWP00001V026 included in
FW01070V010 or later version.
NOTE! These parameters are shown, when P17.2 = 0.
5.16 Fault autoreset parameters (Control panel: Menu PAR -> P14)
NOTE! These parameters are shown, when P17.2 = 0.
P13.25
Temperature fault
input
1 7 1 739
Binary-coded selection
of signals to use for
alarm and fault trigger-
ing
B0 = Temperature input 1
B1 = Temperature input 2
B2 = Temperature input 3
NOTE! Hidden until an
OPTBH board is con-
nected
P13.26
Temperature fault
mode
0 2 2 743
0 = Not used
1 = Low limit
2 = High limit
P13.27
Temperature fault
limit
-50.0/
223.2
200.0/
473.2
100.0 742
Temperature fault
threshold, hidden until
an OPTBH board is con-
nected
Input phase fault* 0 3 3 730
As parameter P13.3
Motor tempera-
ture
memory mode*
0 2 2 15521
0 =
disabled
1 =
constant mode
2 =
last value mode
Code Parameter Min Max Unit Default ID Note
Automatic Reset 0 1 0 731
0 = Disabled
1 = Enable
Wait time 0.10 10.00 s 0.50 717 Waiting time after fault
Trial time 0.00 60.00 s 30.00 718 Maximum time for trials
Trials number 1 10 3 759 Maximum trials
Restart Function 0 2 2 719
0 = Ramping
1 = Flying
2 = From Start Function
Table 19: Fault autoreset parameters
Code Parameter Min Max Unit Default ID Note
Table 18: Protections