30 • vacon modbus
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
6
6.2.5
Parameters
The parameter addresses are determined in the application. Every parameter has been given an ID
number in the application. The ID numbering of the parameter as well as the parameter ranges and
steps can be found in the application manual in question. The parameter value shall be given without
decimals. The following functions can be activated with parameters:
Function code
Function
Modbus Address
Parameter ID’s
03 Read Holding Registers 30101…31999 101-1999
04 Read Input Registers 40101…41999 101-1999
06 Preset Single Register 40101…41999 101-1999
16
Preset Multiple
Registers
40101…41999
101-1999
Table 17. Parameters
6.2.6
Actual values
The actual values as well as parameter addresses are determined in the application. Every actual
value has been given an ID number in the application. The ID numbering of the actual values as well
as the value ranges and steps can be found in the application manual in question. The following func-
tions can be activated with parameters:
Function code
Function
Actual values
03 Read Holding Registers 30001-30098
04 Read Input Registers 40001-40098
Table 18. Actual values