21Installation Manual auroMATIC 560
Display Turn the dial to adjust Setting range Factory setting
Setting the max. temperature
for cylinder 2
20 - 80 °C 60 °C
Setting the activation difference for cylinder 2
(The activation difference should always
be 2 K greater than the deactivation differ-
ence)
5 – 12 K 7 K
Setting the deactivation difference for cylin-
der 2
(The deactivation difference should always
be 2 K less than the activation difference)
1 – 10 K 3 K
Activating the anti-Legionnaire‘s disease
program
0=off; 1=day; 2=night 0=off
Activating the reheating delay function 0=deactivated; 1=activated 0
Activating duration controlling 0=off; 1=on 0
Setting the current day 1 - 31 0
Setting the current month 1 - 12 0
Setting the current year 2000 - 2015 2000
Table 6.1 System parameters (continued)
Start-up 6