5 Installation
14 Installation and maintenance instructions ecoTEC plus 0020209591_01
4.9 Removing the front casing
Remove the front casing as shown in the illustration.
4.10 Removing the side section
2x
Caution.
Risk of material damage caused by mech-
anical deformation.
Removing both side sections may cause
mechanical distortion in the product, which
may cause damage to the piping, for ex-
ample, and potentially result in leaks.
Always remove only one side section
never both side sections at the same time.
Remove the side section as shown in the illustration.
5 Installation
Danger!
Risk of scalding and/or risk of material
damage due to incorrect installation lead-
ing to escaping water.
Stresses in supply lines can cause leaks.
Install the supply lines without tension.
Caution.
Risk of material damage due to the gas
leak-tightness test.
At a test pressure of >11 kPa (110 mbar), gas
leak-tightness tests may cause damage to
the gas valve.
If, during gas leak-tightness tests, you
also place the gas lines and the gas valve
in the product under pressure, use a max.
test pressure of 11 kPa (110 mbar).
If you cannot limit the test pressure to
11 kPa (110 mbar), close any gas isolator
cocks that are installed upstream from the
product before you carry out the gas leak-
tightness test.
If, during gas leak-tightness tests, you
have closed the gas isolator cock that is
installed upstream of the product, relieve
the gas line pressure before you open this
gas isolator cock.
Caution.
Risk of material damage due to corrosion.
If non-diffusion-tight plastic pipes are used
in the heating installation, this may cause
air to enter the heating water and corrosion
of the heat generation circuit and the heat
generator.
If using non-diffusion-tight plastic pipes
in the heating installation, partition the
system by installing an external heat ex-
changer between the heat generator and
the heating installation.
Caution.
Risk of material damage due to heat trans-
fer during soldering.
Do not solder the connection pieces if
the connection pieces are screwed to the
service valves.