Start-up 7
0020209591_01 ecoTEC plus Installation and maintenance instructions 21
7.3.4 Target feed temperature, hot water
temperature, Comfort mode
1. To set the target flow temperature, hot water temperat-
ure and Comfort mode, use
and .
2.
Press
to confirm this setting.
7.3.5 Heating partial load
The heating partial load of the product is set to Auto at the
factory. The product independently determines the optimum
heating output depending on the current heat demand of
the system. You can retroactively change the setting in the
Diagnostics menu under D.000.
7.3.6 Auxiliary relay and multi-functional module
1. If you have connected additional components to the
product, assign these components to the individual re-
lays.
2.
In each case, confirm by pressing
.
Note
This setting can be retroactively changed in
the Diagnostics menu using D.026, D.027
and D.028.
7.3.7 Contact data
If required, store your telephone number in the Appli-
ance config. (max. 16 digits/no blank spaces). The oper-
ator can view the telephone number.
7.3.8 Ending the installation assistant
Once you have run through the installation assistant suc-
cessfully, confirm by pressing
.
The installation assistant will close and will not launch
again when the product is next switched on.
7.4 Restarting the installation assistants
Menu Installer level Start inst. assistant
You can restart the installation assistant at any time by call-
ing it up in the menu.
7.5 Test programmes
Menu Installer level Test programs
As well as the installation assistants, you can also call up
the following test programmes for start-up, service and
troubleshooting.
Check programs
Function menu
Electronics self-test
7.6 Performing a gas family check
Danger!
Risk of poisoning!
Inadequate combustion quality (CO), indic-
ated by F.92/93, leads to an increased risk of
poisoning.
Make sure that the fault is completely
eliminated before starting up the product
for continuous operation.
Menu Installer level Test programs Gas family
check
The gas family check checks the product setting with regard
to combustion quality.
Note
If additional condensing units are connected to the
same flue gas pipe in the heating installation, en-
sure that none of these condensing units are in
operation or start operating throughout the entire
test programme, so that the test result is not dis-
torted.
Perform the gas family check as part of routine product
maintenance work, after replacing components, carrying
out work on the gas route and following gas conversion.
Result Meaning Measure
F.92 See the table of
fault codes in the
appendix
See the table of fault
codes in the appendix
"Successful" Combustion
quality is good.
Unit configur-
ation matches
the specified gas
group.
None
"Warning" Combustion
quality inad-
equate.
CO content is
incorrect.
Start check programme
P.01 and adjust the
CO content with the
adjusting screw in the
Venturi.
If the correct CO con-
tent cannot be set:
Check that the gas re-
strictor is correct (yellow:
G20 natural gas, blue:
G25 natural gas, grey:
Liquid gas) and undam-
aged.
Repeat the gas family
check.
F.93 See the table of
fault codes in the
appendix
See the table of fault
codes in the appendix
Note
It is not possible to perform CO measure-
ments during the gas family check.