7 Start-up
22 Installation and maintenance instructions ecoTEC plus 0020209591_01
7.7 Using check programmes
Menu → Installer level → Test programs → Check pro-
grams
Display Meaning
P.00 Purging check programme:
The internal pump is cyclically actuated.
The heating circuit and the hot water circuit are
purged via the automatic air vent (the cap of the
automatic air vent must be released).
1 x
: Start heating circuit purging
2 x ( ): Start hot water circuit purging
3 x
( ): Restart heating circuit purging
1 x (Cancel): End purge programme
Note
The purge programme runs for 7.5 min per circuit
and then terminates.
Purging the heating circuit:
Diverter valve in heating position, actuation of in-
ternal pump for 9 cycles: 30 sec. on, 20 sec. off.
Display: Active heating circuit.
Purging the hot water circuit:
After the above-mentioned cycles have run or the
right-hand selection button has been pressed again:
Diverter valve in the hot water position, actuation
of the internal pump as above. Display: Active hot
water circuit.
P.01 Maximum load check programme:
After successful ignition, the product is operated at
maximum heat input.
P.02 Minimum load check programme:
After successful ignition, the product is operated at
minimum heat input.
P.06 Filling mode check programme:
The diverter valve is moved to the mid-position. The
burner and pump are switched off (to fill or drain the
product).
7.8 Checking and treating the heating
water/filling and supplementary water
Caution.
Risk of material damage due to poor-qual-
ity heating water
▶ Ensure that the heating water is of suffi-
cient quality.
▶ Before filling or topping up the system, check the quality
of the heating water.
Checking the quality of the heating water
▶ Remove a little water from the heating circuit.
▶ Check the appearance of the heating water.
▶ If you ascertain that it contains sedimentary materials,
you must desludge the system.
▶ Use a magnetic rod to check whether it contains mag-
netite (iron oxide).
▶ If you ascertain that it contains magnetite, clean the sys-
tem and apply suitable corrosion-protection measures, or
fit a magnet filter.
▶ Check the pH value of the removed water at 25 °C.
▶ If the value is below 8.2 or above 10.0, clean the system
and treat the heating water.
▶ Ensure that oxygen cannot get into the heating water.
▶ Ensure that oxygen cannot get into the heating water.
(→ Page 27)
Checking the filling and supplementary water
▶ Before filling the system, measure the hardness of the
filling and supplementary water.
Treating the filling and supplementary water
▶ Observe all applicable national regulations and technical
standards when treating the filling and supplementary
water.
Provided the national regulations and technical standards
do not stipulate more stringent requirements, the following
applies:
You must treat the heating water in the following cases:
– If the entire filling and supplementary water quantity dur-
ing the operating life of the system exceeds three times
the nominal volume of the heating installation, or
– If the guideline values listed in the following table are not
met, or
– If the pH value of the heating water is less than 8.2 or
more than 10.0.
Total
heating
output
Water hardness at specific system volume
1)
≤ 20 l/kW
> 20 l/kW
≤ 50 l/kW
> 50 l/kW
kW
ppm
CaCO₃
mol/m³
ppm
CaCO₃
mol/m³
ppm
CaCO₃
mol/m³
< 50 < 300 < 3 200 2 2 0.02
> 50
to ≤ 200
200 2 150 1.5 2 0.02
> 200
to ≤ 600
150 1.5 2 0.02 2 0.02
> 600 2 0.02 2 0.02 2 0.02
1) Nominal capacity in litres/heating output; in the case of multi-
boiler systems, the smallest single heating output is to be used.
Caution.
Risk of material damage if the heating
water is treated with unsuitable additives.
Unsuitable additives may cause changes in
the components, noises in heating mode and
possibly subsequent damage.
▶ Do not use any unsuitable frost and cor-
rosion protection agents, biocides or seal-
ants.
No incompatibility with our products has been detected to
date with proper use of the following additives.
▶ When using additives, follow the manufacturer's instruc-
tions without exception.
We accept no liability for the compatibility of any additive or
its effectiveness in the rest of the heating system.
Additives for cleaning measures (subsequent
flushing required)
– Fernox F3