0020288151_04 Operating and installation instructions 61
Code/meaning Possible cause Measure
HP control module MO2 con-
figuration not correct
F.1249
Incorrectly connected FM5 1. Remove the FM5.
2. Select another configuration.
FM5 configuration not correct
F.1251
Incorrect set value for the FM5 Set the correct set value for the FM5.
FM3 configuration [1] MO not
correct (can be address 1 to
3)
F.1257…F.1259
Incorrect component selection
for the MO
Select the component in the FM3 MO function that is appropri-
ate for the connected component on the FM3's multi-function
output.
FM5 configuration MO not
correct
F.1263
Incorrect component selection
for the MO
Select the component in the FM5 MO function that is appropri-
ate for the connected component on the FM5's multi-function
output.
Sys. control room temperat-
ure sensor signal invalid
F.1361
Room temperature sensor de-
fective
Replace the control.
Room temp. sensor signal on
remote control 1 invalid (can
be address 1 to 3)
F.1363…F.1366
Room temperature sensor de-
fective
Replace the remote control.
S1 sensor signal at FM3 ad-
dress 1 invalid (can be S1 to
7 and address 1 to 3)
F.5000…F.5020
Sensor defective Replace the sensor.
S1 sensor signal at FM5 in-
valid (can be S1 to S13)
F.5021…F.5033
Sensor defective Replace the sensor.
Heat generator 1 reports
faults (can be heat generator 1
to 8)
F.5034…F.5049
Fault in the heat generator See the instructions for the heat generator displayed.
Ventilation unit reports faults
F.5050
Ventilation unit fault See instructions for the ventilation unit.
HP control module reports
faults
F.5051
Fault in the heat pump control
module
Replace the heat pump control module.
Assignment of remote control
1 missing (can be address 1
to 3)
F.5056…F.5059
The assignment of remote con-
trol 1 to the zone is missing.
Assign the correct address to the remote control in the Zone
assignment: function.
Zone activation missing
F.5060
A zone that is in use is not yet
activated.
In the Zone activated: function, select the value Yes.
Heating circuits inactive In the Circuit type: function, define the required function for
the heating circuit.
B.3 Maintenance messages
# Code/meaning Description Maintenance work Interval
1 Heat generator
1 requires main-
tenance *, * Can
be heat generator
1 to 8
The heat generator requires
maintenance work.
Refer to the operating or install-
ation instructions for the relev-
ant heat generator for informa-
tion on the maintenance work
required
See the operating or installation
instructions for the heat gener-
ator
2 Ventilation unit
requires main-
tenance
The ventilation unit requires
maintenance work.
Refer to the operating or install-
ation instructions for the relev-
ant ventilation unit for informa-
tion on the maintenance work
required
See the operating or installation
instructions for the ventilation
unit
3 Water defi-
ciency: Follow
the instructions
in the heat gen.
The water pressure is too low in
the heating installation.
Water deficiency: Follow the in-
structions in the heat generator
See the operating or installation
instructions for the heat gener-
ator
4 Maintenance
Contact:
Date on which maintenance is
due for the heating installation.
Carry out the required mainten-
ance work
Date entered in the control