EasyManuals Logo

Vaillant VWL 127/5 IS User Manual

Vaillant VWL 127/5 IS
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
Appendix
0020257319_02 Hydraulic station Installation and maintenance instructions 51
Statuscode Meaning
S.240 Compr. oil temp. too
low, environment too cold
The compressor heating is switched on. The unit does not start up.
S.252 Fan unit 1: Fan blocked If the fan speed is 0 rpm, the heat pump is switched off for 15 minutes and then restarted. If the fan
does not start up after four unsuccessful restarts, the heat pump is switched off and the fault mes-
sage F.718 is displayed.
S.255 Fan unit 1: Air inlet
temp. too high
The compressor does not start because the outdoor temperature at the fan is above the operating
limits. Heating mode: > 43 °C. Domestic hot water mode: > 43 °C. Cooling mode: > 46 °C.
S.256 Fan unit 1: Air inlet
temp. too low
The compressor does not start because the outdoor temperature at the fan is below the operating
limits. Heating mode: < -20 °C. Domestic hot water mode: < -20 °C. Cooling mode: < 15 °C.
S.260 Fan unit 2: Fan blocked If the fan speed is 0 rpm, the heat pump is switched off for 15 minutes and then restarted. If the fan
does not start up after four unsuccessful restarts, the heat pump is switched off and the fault mes-
sage F.785 is displayed.
S.272 Building circuit: Re-
maining feed head limit active
The remaining feed head that is set under the configuration is reached.
S.273 Building circuit: Flow
temperature too low
The flow temperature that is measured in the building circuit is below the operating limits.
S.275 Building circuit: Flow
rate too low
Building circuit pump defective. All consumers in the heating system are closed. Flow rate is too low
for recording with the volume flow sensor (< 120 l/h). The values fall below the specific minimum
volume flows. Check that the dirt filter is permeable. Check the stopcocks and thermostatic valves.
Ensure that the flow rate is at least 35% of the nominal flow rate. Check that the building circuit pump
functions correctly.
S.276 Building circuit: Lock-
out contact S20 open
Contact S20 is open at the heat pump's main PCB. Incorrect limit thermostat setting. Flow temper-
ature sensor (heat pump, gas-fired boiler, system sensor) measures values that deviate downwards.
Adjust the maximum flow temperature for the direct heating circuit via the system control (observe
the upper switch-off threshold for the boilers). Adjust the set value for the limit thermostat. Check the
sensor values
S.277 Building circuit: Pump
fault
If the building circuit pump is inactive, the heat pump is switched off for 10 minutes and is then restar-
ted. If the building circuit pump does not start up after three unsuccessful restarts, the heat pump is
switched off and the fault message F.788 is displayed.
S.280 Freq. converter fault:
Compressor
The compressor motor or wiring is defective.
S.281 Freq. converter fault:
Mains voltage
There is overvoltage or undervoltage.
S.282 Freq. converter fault:
Overheating
If the cooling of the frequency inverter is not sufficient, the heat pump is switched off for one hour and
then restarted again. If the cooling is not sufficient after three unsuccessful restarts, the heat pump is
switched off and the fault message F.819 is displayed.
S.283 De-icing time too long If the de-icing takes longer than 15 minutes, the heat pump is restarted. If the time for the de-icing is
still not sufficient after three unsuccessful restarts, the heat pump is switched off and the fault mes-
sage F.741 is displayed. Check whether sufficient thermal energy is available from the building cir-
cuit.
S.284 De-icing flow temperat-
ure too low
If the flow temperature is below 5 °C, the heat pump is restarted. If the flow temperature is still not
sufficient after three unsuccessful restarts, the heat pump is switched off and the fault message F.741
is displayed. Check whether sufficient thermal energy is available from the building circuit.
S.285 Compressor outlet tem-
perature too low
Compressor outlet temperature is too low
S.286 Hot gas temperature
switch open
If the hot gas temperature is above 119 °C +5 K, the heat pump is switched off for one hour and then
restarted again. If the hot gas temperature has not fallen after three unsuccessful restarts, the heat
pump is switched off and the fault message F.823 is displayed.
S.287 Fan 1: Wind Before starting, the fan rotates at a speed of 50 rpm or higher. This may be caused by a strong out-
side wind.
S.288 Fan 2: Wind Before starting, the fan rotates at a speed of 50 rpm or higher. This may be caused by a strong out-
side wind.
S.289 Current limit active The outdoor unit's power consumption is reduced, the compressor speed is reduced. The com-
pressor's operating current exceeds the limit value that is set under the configuration. (for 3 kW,
5 kW, 7 kW units: <16 A; for 10 kW, 12 kW units: <25 A)
S.290 Switch-on delay active The compressor's switch-on delay is active.
S.302 High-pressure switch
open
If the pressure in the refrigerant circuit exceeds the operating limit, the heat pump is switched off for
15 minutes and is then restarted again. If the pressure remains too high after four unsuccessful re-
starts, the fault message F.731 is displayed.
S.303 Compressor outlet tem-
perature too high
The operating characteristics have been exited. The heat pump is restarted.
S.304 Evaporation temperat-
ure too low
The operating characteristics have been exited. The heat pump is restarted.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant VWL 127/5 IS and is the answer not in the manual?

Vaillant VWL 127/5 IS Specifications

General IconGeneral
BrandVaillant
ModelVWL 127/5 IS
CategoryHeat Pump
LanguageEnglish

Related product manuals