60 Installation and maintenance instructions Hydraulic station 0020257319_02
Temperature (°C) Resistance (ohms)
90 918
95 788
100 680
105 588
110 510
P Characteristic values for the VR10 internal temperature sensors, cylinder temper-
ature
Temperature (°C) Resistance (ohms)
-40 88130
-35 64710
-30 47770
-25 35440
-20 26460
-15 19900
-10 15090
-5 11520
0 8870
5 6890
10 5390
15 4240
20 3375
25 2700
30 2172
35 1758
40 1432
45 1173
50 966
55 800
60 667
65 558
70 470
75 397
80 338
85 288
90 248
95 213
100 185
105 160
110 139
115 122
120 107
125 94
130 83
135 73
140 65
145 58
150 51