Vaisala HUMICAP HMW92 - Chapter 4 Operation

Vaisala HUMICAP HMW92
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User's Guide _______________________________________________________________________
32 ___________________________________________________________________ M211399EN-G
Wiring HMW95
The RS-485 line of the transmitter is isolated from the power supply. A
separate ground reference terminal (GND) is provided for the RS-485
connection.
If you are using a shielded cable, you can use the Shld terminal to hold
the exposed part of the shield. Note that the Shld terminal is floating
(not electrically connected).
1209-014
Figure 23 Wiring HMW95
Connecting Several Transmitters on Same RS-485
Line (HMW95)
Set the RS-485 termination jumper to “ON” on the transmitter that is at
the end of the line. This terminates the line with a 120 Ω resistor. For
location of the jumper, see section Transmitter Parts - Inside on page 6.
Connect the cable shield to ground on the building controller side.
1209-015
Figure 24 Several Transmitters on Same RS-485 Line
D- -VsD+ +Vs
+
-
Power supply
18 ... 35 VDC
or 24 VAC ±20%
RS-485
Shld GND
Tr
ans
mit
ter
D-
-Vs
D+
+V
s
Shld
GND
Building control
ler Tran
smi
tter
Tra
nsm
itt
er
P
owe
r
s
upply
D-
D+
+Vs
-Vs
GND
SH
IELD
RS-485:
BA
Cnet or
MO
DBU
S
mas
ter
C
onnect shield
on cont
roller side
Set
RS-485
t
ermination ju
mper
D-
-Vs
D+
+Vs
Shld
GND
D-
-V
s
D+
+
Vs
Shld
GND