Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 47
Aout 2 range ( V) : 0.00 ... 5.00 (error: 5.50)
Example (set channel 1 to 0 ... 1 V output, with error level at 2 V):
>amode 1 0 1 2
Aout 1 range ( V) : 0.00 ... 1.00 (error: 2.00)
Set Analog Output Scaling
Use the ASEL command to select the output parameter and scaling for
analog output channels.
ASEL [channel parameter lo_value hi_value]<cr>
Analog output channel, 1 or 2.
Parameter that is output on the channel.
Available
parameters are:
relative humidity
temperature
dew/frost point temperature
dew point temperature
wetbulb temperature
enthalpy
mixing ratio
absolute humidity
dTd dew/frost point depression
Low limit of the scaling, in the units of the selected
parameter.
High limit of the scaling in the units of the selected
parameter.
Example (set channel 1 to output dewpoint, in the range -10 ... 20 °C):
>pass 9000
>asel 1 TD -10 20
Aout 1 quantity : Td (-10.00 ... 20.00 'C)