EasyManua.ls Logo

VAT Series 651 - 3.11 Logic interface

VAT Series 651
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, Operating & Maintenance Instructions
Series 651 DN 320-400 (I.D. 12“ - 16”), Logic
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
267736ED
2008-02-26
28/53
3.10.2.4 Valve speed adjustment
Valve speed effects:
Response time
Default value is 1000. Adjustment range is from 1 to 1000.
This parameter effects valve plate actuating speed.
Speed adjustment is effective for PRESSURE CONTROL and POSITION CONTROL.
Note: Normally best pressure control response is achieved with max. valve speed. In particular applications it may be of
advantage to have a slower valve response.
Note: OPEN and CLOSE are always done with max. speed.
Adjustment procedure:
1. Use optimal gain factor, sensor delay time and setpoint ramp according to preceding tuning steps.
2. Open valve.
3. Control a typical pressure / flow situation.
4. Repeat from step 2 with slower valve speed until required response is achieved.
Local operation:
(‘Control View’, ‘Control Performance Analyzer’ or
‘Service Box 2‘)
Remote operation:
Do configuration in menu ‘Setup / Control Parameter’.
Note: It’s not possible to do ‘Interface configuration‘
via remote operation.
3.11 Logic interface
Default configuration:
OPEN input CLOSE input OPEN output CLOSE output
not inverted not inverted open close

Related product manuals