EasyManua.ls Logo

Veeder-Root TLS-4 Series - CSLD Problem 10 - Tank 8 Failing

Veeder-Root TLS-4 Series
87 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 CSLD Troubleshooting
Actual CSLD Test Problems Analyzed
10-36
CSLD PROBLEM 10 - TANK 8 FAILING
Diagnostics
I61200
MAY 7, 1999 10:10 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL MANIFOLDED TANKS
1 DIESEL 1 2, 3, 4, 5
2 DIESEL 2 1, 3, 4, 5
3 DIESEL 3 1, 2, 4, 5
4 DIESEL 4 1, 2, 3, 5
5 DIESEL 5 1, 2, 3, 4
6 AUTO DIESEL NONE
7 SUPER NONE
8 REGULAR 1 9
9 REGULAR 2 8
10 NONE
11 NONE
12 NONE
IA5200
MAY 7, 1999 10:11 AM
CSLD DIAGNOSTICS: RATE TEST
TK DATE LRATE INTVL ST AVLRTE VOL C1 C3 FDBK ACPT THPUT DFMUL RJT
6 9905070326 -0.013 41.1 1 0.000 7740 80 22 45.0 44.8 0.86 -0.36 0
7 9905070456 0.003 22.2 1 0.014 4823 58 23 20.3 16.9 0.87 0.18 1
8 9905070428 0.246 6.8 8 0.241 8708 11 10 0.0 0.0 2.86 0.79 12
IA5100
MAY 7, 1999 10:11 AM
T 8:REGULAR 1
TIME ST LRT AVTMP TPTMP BDTMP TMRT DSPNS VOL INTVL DEL ULLG THPT
9904120309 0 0.395 64.3 67.8 71.5 -0.02 980 8808 36.0 36.8 909 3.0
9904130447 0 0.213 64.8 68.5 72.3 -0.01 849 5892 23.0 62.7 1038 3.0
9904280337 0 0.226 67.1 68.9 70.0 -0.02 608 6015 63.5 75.2 1028 3.1
9904280451 0 0.244 67.1 68.9 70.1 -0.03 578 6013 36.5 76.4 1028 3.1
9904300319 0 0.198 64.8 68.5 72.3 0.05 1102 10406 26.5 15.5 835 3.1
9905030233 0 0.130 65.9 69.9 74.2 0.01 1124 12183 22.0 17.1 762 3.1
9905030302 6 -0.032 65.9 69.9 74.2 0.01 983 12183 117.5 17.8 762 3.1
9905040303 0 0.324 66.8 70.7 74.7 -0.00 902 9501 29.5 41.7 877 2.8
9905040453 0 0.178 66.8 70.6 74.6 -0.01 856 9453 46.5 43.3 879 2.8
9905050339 0 0.186 67.4 71.0 74.8 -0.00 697 11738 90.0 10. 785 2.8
9905070428 0 0.370 68.2 71.8 75.1 -0.02 719 7068 37.0 59.0 983 2.9
Manifolded set.