Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 102
Function Code: 62D Version 1
Function Type: Set Enable/Disable Tank Leak Test Fail Alarms
Command Format: Inquire:
Display: <SOH>S62DTTgpa <SOH>I62DTT
Computer: <SOH>s62DTTgpa <SOH>i62DTT
Typical Response Message, Display Format:
<SOH>
I62D01
22-05-01 15:10
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 REGULAR UNLEADED GROSS TEST FAIL DISABLED
PERIODIC TEST FAIL DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i62DTTYYMMDDHHmmTTgpa
TTgpa&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. g - Gross Test Fail Alarm
0 = Disabled
1 = Enabled
4. p - Periodic Test Fail Alarm
0 = Disabled
1 = Enabled
5. a - Annual Test Fail Alarm
0 = Disabled
1 = Enabled
6. && - Data Termination Flag
7. CCCC - Message Checksum