Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 101
Function Code: 62A Version 1
Function Type: Set Tank Annual Leak Test Minimum Volume
Command Format: Inquire:
Display: <SOH>S62ATTGGGGGG <SOH>I62ATT
Computer: <SOH>s62ATTFFFFFFFF <SOH>i62ATT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. GGGGGG - Annual Test Minimum Volume, Gallons (Decimal)
3. FFFFFFFF - Annual Test Minimum Volume, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I62A01
22-05-01 15:10
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR UNLEADED 0
<ETX>
Typical Response Message, Computer Format:
<SOH>i62ATTYYMMDDHHmmTTFFFFFFFF
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Annual Test Minimum Volume, Gallons (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum