Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 100
Function Code: 629 Version 1
Function Type: Set Tank Delivery Required Limit
Command Format: Inquire:
Display: <SOH>S629TTGGGGGG <SOH>I629TT
Computer: <SOH>s629TTFFFFFFFF <SOH>i629TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. GGGGGG - Delivery Required Limit, Gallons (Decimal)
3. FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I62901
22-05-01 15:10
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNLEADED 900
<ETX>
Typical Response Message, Computer Format:
<SOH>i629TTYYMMDDHHmmTTFFFFFFFF
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Delivery Required Limit, Gallons (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum