Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 105
Function Code: 636 Version 1
Function Type: Set Tank Periodic Leak Test Minimum Volume
Command Format: Inquire:
Display: <SOH>S636TTGGGGGG <SOH>I636TT
Computer: <SOH>s636TTFFFFFFFF <SOH>i636TT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. GGGGGG - Periodic Test Minimum Volume, Gallons (Decimal)
3. FFFFFFFF - Periodic Test Minimum Volume, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I63601
22-05-01 15:10
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR UNLEADED 0
<ETX>
Typical Response Message, Computer Format:
<SOH>i636TTYYMMDDHHmmTTFFFFFFFF
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Periodic Test Minimum Volume, Gallons (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum