Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 109
Function Code: 645 Version 6
Function Type: Set Tank GOST Volume Correction Enable
Command Format: Inquire:
Display: <SOH>S645TTf <SOH>I645TT
Computer: <SOH>s645TTf <SOH>i645TT
Typical Response Message, Display Format:
<SOH>
I645TT
AUG 15, 2011 3:11 PM
TANK GOST VOLUME CORRECTION ENABLE
TANK PRODUCT LABEL GOST VOLUME CORRECTION
1 REGULAR UNLEADED DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i645TTYYMMDDHHmmTTf...
TTf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00=all)
3. f - GOST Volume Correction Enable Flag
0 = Disabled
1 = Enabled
4. && - Data Termination Flag
5. CCCC - Message Checksum