EasyManua.ls Logo

Veeder-Root TLS2 - Page 113

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 110
Function Code:
647 Version 6
Function Type: Set Tank Multipoint Chart Profile
Command Format: Inquire:
Display: <SOH>S647TTf <SOH>I647TT
Computer: <SOH>s647TTf <SOH>i647TT
Notes:
1. TT - Tank Number (Decimal, 00 all)
2. f - Enable = ‘1’.
To disable change profile to 1,4,20 points or linear.
Typical Response Message, Display Format:
<SOH>
I647TT
AUG 15, 2011 3:11 PM
MULTIPOINT TANK CHART ENABLE
CHART NUM CHART
TANK VALID POINTS ENABLED
1 YES 400 YES
2 YES 80 NO
3 YES 168 NO
4 YES 50 NO
5 NO 0 NO
6 NO 0 NO
<ETX>
Typical Response Message, Computer Format:
<SOH>i647TTYYMMDDHHmmTTf...
TTf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00=all)
3. v - Multipoint Tank Chart valid
4. nnnn - Number of points
5. f - Enabled, ‘1’ = yes, ‘0’ = no
4. && - Data Termination Flag
5. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2