Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 122
Function Code: 88C Version 1
Function Type: Set Modem Dial-Out Setup String
Command Format: Inquire:
Display: <SOH>S88CPPaaaaaaaaaaaaaaaaaaaa <SOH>I88CPP
Computer: <SOH>s88CPPaaaaaaaaaaaaaaaaaaaa <SOH>i88CPP
Notes:
1. PP - Communication Port Number (Decimal 01 - 02)
Typical Response Message, Display Format:
<SOH>
I88C01
22-05-01 15:12
COMM BOARD : 1
MODEM SETUP STRING :
<ETX>
Typical Response Message, Computer Format:
<SOH>i88CPPYYMMDDHHmmaaaaaaaaaaaaaaaaaaaa&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. a - Dial Out String (20 ASCII characters)
3. && - Data Termination Flag
4. CCCC - Message Checksum