Part No. 577013-767, Revision H 123
Function Code: 893 Version 4
Function Type: Acknowledge Tank Event Ready Status
Command Format: Inquire:
Display: <SOH>S89300149 <SOH>I89300
Computer: <SOH>s89300149 <SOH>i89300
Notes:
1. 149 - This verification code must be sent to confirm the command
Typical Response Message, Display Format:
<SOH>
I89300
22-05-01 14:58
Tank Delivery Ready Shift Ready Alarm Notice
===================================================
1 Yes No No
2 No No No
<ETX>
Typical Response Message, Computer Format:
<SOH>i89300YYMMDDHHmmNNttnndsa...
NNttnndsa&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. NN - Number of Tanks to follow (Decimal)
3. tt - Tank Number (Decimal)
4. nn - Number of Events to follow (Decimal)
5. d - Delivery Ready Status (0=not ready, 1=Ready)
6. s - Shift Ready Status (0=not ready, 1-4[shift number]=Ready)
7. a - Alarm Notice Status (0=not ready, 1=Ready)
8. && - Data Termination Flag
9. CCCC - Message Checksum