Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 129
Function Code: 8C5 Version 4
Function Type: Set TCP/IP Remote IP Address
Command Format: Inquire:
Display: <SOH>S8C500aaa.aaa.aaa.aaa <SOH>I8C500
Computer: <SOH>s8C500AAAAAAAA <SOH>i8C500
Notes:
1.aaa.aaa.aaa.aaa - Remote Address (decimal)
2. AAAAAAAA - Remote Address (ASCII hex, two digits represent each field)
Typical Response Message, Display Format:
<SOH>
S8C500
JAN 31, 2008 9:02 AM
TCPIP SETUP PARAMETERS
REMOTE IP ADDRESS: 10.2.2.5
<ETX>
Typical Response Message, Computer Format:
<SOH>s8C500YYMMDDHHmmvAAAAAAAA&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. v - Valid Data Flag
0 = Not Valid
1 = Valid
3. AAAAAAAA - Remote Address (ASCII hex, two digits represent each field)
4. && - Data Termination Flag
5. CCCC - Message Checksum